A no-heat call in Henderson tends to arrive after dark, often on a windy night when the desert chill falls fast. I have crawled into more attics than I can count in January, headlamp cutting through insulation dust, listening for a reluctant inducer motor or a gas valve that will not open. Most no-heat situations are fixable without drama, but the first hour matters. Safety comes first, then a methodical check of the obvious, then a short list of decisive actions that either restore heat or set you up for a swift professional repair.
This guide is the sequence I teach new techs and homeowners alike for furnace repair in Henderson. It reflects what fails in our climate, how local building stock is configured, and what you can realistically handle in the moment. It will also help you speak clearly with an HVAC technician, whether you call for furnace repair Henderson services at midnight or book a morning visit.
Know your system before it fails
Henderson homes typically heat with one of three setups: gas furnace paired with a split AC, a heat pump system that provides both heating and cooling, or a package unit on the roof that handles everything. Older townhomes lean toward gas furnaces in closets or garages. Newer builds often run heat pumps, especially in communities where gas isn’t stubbed to every lot. Commercial spaces mix it up, from rooftop packaged units to variable refrigerant systems, so commercial HVAC Henderson service tickets can look different from residential.
Take three minutes on a calm day to find your equipment. Note the following: location of the furnace or air handler, where the filter sits, the electrical disconnect or breaker, and whether there is a visible condensate drain line. If your thermostat has batteries, check what type it needs. Write it down on a piece of painter’s tape on the inside of the return grille. When the system quits at 10 pm, you won’t want to hunt for a 3A blade fuse or coin cell battery.
Safety first when a furnace won’t run
Gas furnaces are designed with safety switches that shut the system down when something’s off. That said, trust your senses. If you smell strong gas, do not try to relight or troubleshoot. Leave the building, call the gas company emergency line, then a qualified HVAC contractor. A faint gas smell when a furnace first lights can be normal, but a persistent odor or hissing is not.
If the furnace is electric or a heat pump, your main safety concern is electrical. Don’t remove service panels unless you are comfortable and you’ve cut power at the breaker or local disconnect. Fan blades and motors can start unexpectedly once a safety switch is restored.
Callidus AirCarbon monoxide deserves a note of its own. Good furnaces vent cleanly, but a cracked heat exchanger or blocked flue can push exhaust into living space. If a carbon monoxide alarm sounds, open windows, step outside, and call for emergency furnace repair Henderson support. Don’t just reset the alarm and resume heat.
Calm triage: what to check in the first 10 minutes
I treat the first ten minutes like a pilot’s checklist. You are confirming power, call for heat, air movement path, and safeties. Small issues cause most no-heat calls, especially after a dust storm or the first cold snap.
- Thermostat check: Confirm the thermostat is set to Heat, the setpoint is higher than room temperature, and the display is on. Replace batteries if the display is dim or unresponsive. If you have a smart stat, try a quick reboot through its menu. If you recently updated Wi-Fi, the stat may have lost settings and defaulted to a schedule that setbacks to 62 overnight. Power and breakers: Furnaces and air handlers typically have two points of power: the main breaker and a local service switch that looks like a light switch nearby. Make sure that local switch is on. At the main panel, scan for any tripped breakers. If a breaker is tripped, switch it fully off, then on. If it trips again immediately, stop and call for HVAC repair Henderson service. Repeated trips indicate a short or failing motor. Filter and airflow: A clogged filter will make a furnace overheat and shut down on a limit switch. Pull the filter and hold it up to light. If you cannot see light through it, it’s clogged. Replace it or run temporarily without it for testing, but only long enough to confirm heat returns. Prolonged operation without a filter will pull dust into the blower and coil. Condensate drain: High efficiency furnaces and almost all heat pumps have condensate safeties. If your air handler sits in the attic, look for a secondary drain pan under it. Water in that pan often triggers a float switch that kills power to prevent ceiling damage. If the pan is wet, you likely have a clogged drain line. You can sometimes clear it with a wet/dry vacuum at the exterior drain termination. If the drain is frozen outside during a rare cold snap, warming sun often clears it by midday. Access panels and door switches: Many furnaces won’t run if the blower door is not fully closed. I find these left ajar after DIY filter swaps. Align the panel and snap it in firmly. The door switch should click.
That handful of checks brings heat back more often than you’d expect. When it doesn’t, it’s time to observe the startup sequence.
Watch the sequence of operations
Modern gas furnaces follow a predictable sequence. Once the thermostat calls for heat, the control board powers the inducer motor. You’ll hear a small fan hum up. A pressure switch confirms draft. The igniter warms for tens of seconds, then the gas valve opens. Burners light with a steady whoosh, and after the heat exchanger warms, the main blower starts.
If you can safely watch through the inspection window, see whether any of those steps fails. A long pause with the inducer running and no glow usually points to an igniter or pressure switch issue. Igniter replacements are common; they are consumables. Another tipoff is the diagnostic LED on the control board visible through a small sight glass. It blinks in patterns that correspond to fault codes. Snap a video of the blinking, count the pattern, and have it ready when you call. It saves time.
Heat pumps follow a different rhythm. The outdoor unit kicks on first, then the indoor blower. If it is particularly cold, the system may engage auxiliary heat strips. If you hear the outdoor fan but no indoor blower, suspect a tripped blower motor or a failed control relay in the air handler. If the outdoor unit won’t start and you see frost, it may be locked in a defrost or a low ambient safety lockout. In Henderson, heat pumps perform well down to the low 40s. Below that, auxiliary heat carries more of the load. A no-heat call for a heat pump often turns out to be a failed heat strip relay or a tripped high-limit on the strips.
What a homeowner can fix without voiding warranties
Some repairs are within reach if you’re comfortable and methodical. Others look simple and go sideways quickly. The line matters, especially with gas and sealed refrigeration systems.
You can safely replace thermostat batteries and even the thermostat itself if you label wires and cut power first. If the thermostat backplate was never leveled and the mercury bubble type was replaced years ago, the system may have been fighting a bad call. Swapping to a modern, correctly configured thermostat often resolves intermittent no-heat symptoms.
You can also replace air filters, reset tripped GFCI outlets that might feed a condensate pump, and clear a minor condensate clog with a wet/dry vacuum. If your furnace has an accessible flame sensor and you are comfortable, removing it with a nut driver and cleaning it with a fine abrasive pad can restore operation. These sensors collect a light layer of oxide and stop confirming flame even when burners light. Handle gently and reinstall in the same position.
What you should not attempt without training: opening a gas line, bypassing a safety switch, swapping a control board, or adding refrigerant. Those require licensed work. I have seen well-meaning homeowners jump a pressure switch to “test” it, only to push exhaust into a living room. If a component failed for a reason, bypassing it just hides the warning, it does not fix the fault.
The short list: no-heat emergency steps that work
When a Henderson furnace quits on a cold evening, workflows help. Here is the tight sequence I coach for getting heat back or making a smart service call.
- Confirm the thermostat call, power at the breaker and service switch, and a clean, properly seated filter. Cycle power to the furnace for two minutes to clear a latched fault. Check the condensate drain and float switches if the air handler sits over living space. Vacuum the exterior drain line for two to three minutes if it is clogged. Observe the startup sequence and note where it stops. Record any control board blink codes with your phone. If you are comfortable, reseat the blower door and inspect for a tripped limit switch. Some have manual reset buttons near the heat exchanger cabinet on older units. If no heat returns, call a reputable HVAC Henderson contractor. Share your notes, thermostat model, and any codes. Ask for availability of furnace repair Henderson technicians and whether they stock common parts for your brand.
That is one list, and it holds up. It is short by design because in an actual no-heat situation, long checklists turn into noise.
Why Henderson furnaces fail more often right after the first cold snap
Every season has its pattern. The first time temperatures drop into the 40s, furnaces that have not run since March wake up. Dust on burners, stiff inducer bearings, and oxidized flame sensors combine to trigger lockouts. Filters that were fine for AC airflow are insufficient for the higher temperature rise of heating. If a return leak pulls attic air, the furnace runs hotter and trips on limit. The outside air in Henderson is dry, but construction dust is relentless, and the extra static from a restrictive filter chokes a marginal blower.
I usually recommend a fall tune-up in October. The visit should include a combustion analysis for gas furnaces, a draft and vent inspection, burner cleaning, ignition check, amperage draws, temperature rise measurement, and filter sizing review. For heat pumps, we verify reversing valve operation, check auxiliary heat, defrost cycles, and electrical connections. AC service Henderson contractors who ignore heating checks leave half the system uninspected.
When it is not the furnace at all
No-heat calls sometimes trace back to building issues. A tripped breaker in a garage subpanel that feeds only the furnace. A dead low-voltage transformer caused by a thermostat wire nicked during a remodel. A smart thermostat powered only by batteries that died at 2 am. One memorable case was a roof-mounted package unit shut down by a windblown tarp left from solar installation. The tarp snuck under the condenser fan guard and jammed the blade, which tripped an internal overload. Removing the obstruction and waiting for the motor to cool solved the problem without parts.
Another frequent culprit is the supply register and return balance. If a homeowner closes too many registers to “push heat to the cold rooms,” static pressure rises and limit switches open. Temperature at the heat exchanger climbs past design range. The system protects itself by shutting off heat, then tries again, then locks out after three strikes. Open the registers and use dampers at the trunk lines if available, not the face of the registers. A good HVAC repair Henderson tech will measure static and show you where the airflow bottlenecks.
Heat pump-specific guidance on cold mornings
Heat pumps get a bad reputation in colder climates, but in the Las Vegas Valley they work well when properly set up. On a chilly morning, you might hear the outdoor unit pause and then reverse briefly. That is the defrost cycle. Steam rising from the unit is often normal. What is not normal is a thick ice shell that never melts, a fan that does not spin for long periods while the compressor runs, or breakers that trip when auxiliary heat engages.
If your heat pump blows cool air inside, check whether the thermostat shows “Aux Heat” or “Emergency Heat.” Emergency heat locks out the heat pump and uses only the electric strips, which can run your meter like a slot machine. If the thermostat was bumped into that mode, switch back to Heat, not Emergency, and see if the outdoor unit starts. If auxiliary heat never engages and the house cannot climb past 65 on a 40 degree morning, you may have a failed heat strip relay or an open high-limit on the air handler. Heat pump repair Henderson technicians carry the common relays and breakers that fail in these scenarios. They also check refrigerant charge by weight and temperature split, not just eyeballing frost.
For rooftop package units and light commercial spaces
Henderson has miles of flat-roof office parks with packaged units exposed to sun and dust. These systems run long hours. No-heat calls often involve failed economizer controls stuck in an open position, worn belts that slip under the higher load of heat mode, or soot at heat exchangers that have seen many seasons. If you manage a space, a simple step like keeping replacement belts on site and knowing where your disconnects are saves a service trip. For commercial HVAC Henderson calls, I always ask for roof access details and any building automation involved. If your unit ties into a building control system, coordinate with your controls contractor when scheduling repairs. Lockouts on the control side can look like equipment failures.
Deciding between repair and replacement on a cold night
Nobody wants to discuss replacement at 9 pm, but sometimes it is the practical path. If your furnace is over 15 years old, has a cracked heat exchanger, or uses an obsolete control board with no parts available, the math leans toward replacement. In Henderson, a matched system upgrade can also improve summer comfort and lower energy bills, not just restore heat.
The bridge plan many homeowners take is to approve the minimum repair that restores safe operation, then schedule a design visit for a full system quote the next day. Good contractors will credit part of your emergency repair toward a replacement if it happens within a set window. When comparing quotes, look at warranty length, parts availability, and details like filter rack upgrades or duct sealing, not just tonnage and AFUE. If you are also considering AC installation Henderson options in the spring, it often costs less to do the full system now than to split the work across seasons.
How to prepare for the tech and shorten the visit
A little prep cuts diagnostic time in half. Clear a path to the furnace or air handler, and if it is in an attic, make sure the access hatch is reachable. Have your filter size handy and set out any prior service records. If you noted blink codes or captured video of startup behavior, send those to the dispatcher. If the home uses a nest of thermostats for different zones, label which one controls the area that is cold.
Share any recent work on the home, like electrical upgrades, water heater replacement that changed venting pressure, or roof work around a flue. A detail as small as a painter moving a thermostat wire from R to Rc can cause a dead heat call that looks like a failed transformer.
Keeping your system ready between seasons
Prevention in our climate is not fancy. Replace filters on time. For most homes, that means every one to three months depending on size and MERV rating. Oversized, high-MERV filters in undersized returns cause more heat limit trips than any other “minor” mistake I see. If your return grille whistles, that is a sign of high static. Consider a return upgrade rather than ever thicker filters.
Schedule two maintenance visits each year, one before cooling season and one before heating. During the heating visit, request a combustion test. Numbers matter. A tech with a combustion analyzer can verify oxygen, carbon monoxide, and efficiency, and spot heat exchanger issues earlier than a visual check. For heat pumps, a careful look at defrost control boards and outdoor sensor placement pays off once cold mornings hit.
If your system sits in the attic, look at the secondary drain pan once a month during winter. A dry pan is a good sign. A slowly filling pan means you have weeks, not months, before the float switch shuts you down on a Sunday night.
When your emergency is also an opportunity
A no-heat moment is stressful, but it can also be the point where you reset your HVAC plan. If this is your second or third emergency in two seasons, step back. Ask your contractor to evaluate duct leakage, load, and equipment match, not just replace parts. I have measured homes where a 1200 square foot footprint carried a 5-ton unit with ductwork sized for 3 tons. On heat, those oversized systems slam to temperature, trip limits, and short cycle. Right-sizing and duct fixes stabilize heat and make summer bearable.
If you manage a small business, consider a service agreement that includes priority dispatch and stocked parts specific to your rooftop model. Commercial HVAC Henderson providers often tag parts bins to your account. When something fails, the tech arrives with the exact board, belt, and contactor your unit needs. That is the difference between a same-day fix and a two-day wait while a part ships.
A note on honest pricing and after-hours calls
Emergency calls cost more for good reasons: staffing, parts inventory, and the impact on next-day schedules. That said, ask for clarity before the tech rolls. Many HVAC repair Henderson companies offer tiered pricing that includes a diagnostic fee and a flat rate per repair. If they quote a range, ask what factors move the price. If they can restore heat temporarily and return during normal hours to finish, that can save money. For example, a tech may safely clean a flame sensor and confirm the furnace runs, then return to replace a weakening igniter under warranty during business hours.
Beware of anyone pushing add-ons you did not ask for in the middle of an emergency, especially duct cleaning packages or magic filters promising miracles. Focus on restoring safe heat. You can revisit upgrades after you sleep.
Where heating meets cooling in Henderson
Our systems do double duty. A healthy furnace cabinet and clean blower matter for cooling airflow in May. If you make improvements now, they pay back in summer. A properly sized and sealed return plenum reduces noise and increases cooling efficiency. A new thermostat configured by someone who understands heat pump logic avoids the common mistake where auxiliary heat runs during mild mornings, inflating bills.
When spring rolls around, if you are contemplating air conditioning repair Henderson or ac installation Henderson options, bring your notes from winter. A tech who listened to your no-heat concerns will size cooling with a clearer picture of your home’s quirks. Oversizing the AC as a reflex to hot rooms makes heat performance worse. Balanced ductwork and measured loads beat tonnage for comfort.
Final thoughts from countless cold-night calls
I have carried more flame sensors and silicone tubing for pressure switches into Henderson attics than I care to admit. The pattern repeats: a clean filter, solid electrical connections, a clear drain, and a tuned ignition system prevent most emergencies. When a no-heat event still finds you, the right steps in the right order restore comfort or set the stage for a quick, professional fix.
If you remember nothing else, remember this: confirm the basics, observe the sequence, do not bypass safeties, and air conditioning repair Henderson call for help with useful details. Whether it is heat pump repair Henderson support you need, traditional furnace service, or full HVAC Henderson system planning, the combination of steady triage and competent service will get your home warm again without drama. Then you can turn to the quieter work of making sure the next cold snap is just another night.